The Geoclima family expands further, introducing the TMH Giant range. This new series, which includes water-cooled chillers, stands out for its powerful, giant compressor: Hanbell RTM100.
This is an oil-free centrifugal compressor with magnetic levitation technology, capable of delivering up to 1400 kW (4,776,998 BTU/h) individually and 4200 kW (14,330,996 BTU/h) in parallel installations. Thanks to its “giant” performance, Hanbell is the ideal solution for both comfort and process applications that require high cooling capacity and an outlet water temperature between 4 and 14°C (39.2 – 57.2°F).
The TMH Giant units, equipped with a flooded evaporator and an optional economizer, offer several key benefits:
Refrigerants and cooling capacity
The range supports R134a and R513A refrigerants, as well as the environmentally friendly HFO-R1234ze, which boasts a GWP of 6 and an ODP of 0. The following are the performance specifications for single and parallel modules, based on the refrigerant used. The data were calculated considering an inlet water temperature of 12°C (53.6°F) and an outlet temperature of 7°C (44.6°F).
SINGLE MODULE
REFRIGERANT | COOLING CAPACITY | E.E.R. |
---|---|---|
HFO-R1234ze | 1200 kW 4,094,570 BTU/h | 6,31 W/W 21.52 BTU/Wh |
R134a | 1400 kW 4,776,998 BTU/h | 6,18 W/W 21.07 BTU/Wh |
R513A | 1400 kW 4,776,998 BTU/h | 6,18 W/W 21.07 BTU/Wh |
3 MODULES IN PARALLEL
REFRIGERANT | COOLING CAPACITY | E.E.R. |
---|---|---|
HFO-R1234ze | 3600 kW 12,283,711 BTU/h | 6,31 W/W 21.52 BTU/Wh |
R134a | 4200 kW 14,330,996 BTU/h | 6,18 W/W 21.07 BTU/Wh |
R513A | 4200 kW 14,330,996 BTU/h | 6,18 W/W 21.07 BTU/Wh |
Optional technologies and accessories
I nostri chiller possono essere personalizzati con una serie di accessori opzionali per venire incontro alle esigenze di ogni applicazione. Gli optional offerti da Geoclima comprendono:
Integrated Pump with Inverter
This option enables water circulation between the chiller and the building’s system. As it is already installed on the unit, there will be no need for extensive on-site connection work.
Special materials
Heat exchangers, including condensers and evaporators, can be constructed from various materials to meet specific project requirements.
Active Harmonic Filter
A device that mitigates harmonic electrical currents that may disrupt the building’s electrical network.
Teslamiser
Geoclima’s new power supply management system for the Turbocor-powered chillers, which consists of an integrated system with a lithium polymer battery and a converter that controls charge and discharge of power to the chiller. An innovative “powerbank” for chillers to manage and optimize energy flows.
Fast Start
This function allows the chiller to reach 100% cooling capacity within a few minutes after switch-on, minimizing downtime in the event of a power failure.
Dual Power Supply
Offers both primary and backup power sources to prevent extended interruptions in chiller operation, maintaining uninterrupted cooling.
Automatic Power Switch (ATS)
An accessory device that automatically transfers power supply from one source to another in case of a power outage or when the primary power source fails, ensuring uninterrupted cooling.
Onboard Touch
An online software that allows local download of chiller data for diagnostics and troubleshooting purposes. Remote monitoring is also available upon request.
Request a quote
Would you like to receive more information on the TMH Giant range? Contact our specialized technicians!